Model Designation and Meaning
Item
Description
①
Manufacturer code
②
Product model
③
Design category
④
Rated operating current
⑤
Phase and wire system code
⑥
Structural unit code
⑦
Special code
Ambient temperature: Between -5°C and +40°C; average temperature over 24 hours shall not exceed +35°C
Relative humidity: Not more than 90% at +20°C
Altitude: Not exceeding 2000 meters
Pollution level: Grade III
Installation category: Class III and IV
For special usage conditions, specific requirements must be stated in the contract; customized manufacturing will be provided accordingly.
Rated insulation voltage: 660V
Rated frequency: 50–60Hz
Insulation resistance: ≥ 20 MΩ for each busway section (users should verify resistance before installation)
Dielectric strength: Each busway section undergoes factory testing with 50Hz/3750V for 1 minute
Short-circuit strength: Busway must withstand the thermal and dynamic stress from rated short-time withstand current and peak withstand current without any permanent visible deformation