The Underground Prefabricated Substation, also known as the Landscape-Type Underground Transformer Substation, is an innovative solution designed for all-weather outdoor operation with a maintenance-free system. It features a low-loss, low-temperature-rise, low-noise, low-radiation, compact, high-corrosion-resistant, fully sealed, and submersible underground transformer. This includes tunnel transformers and underground utility corridor transformers, integrated with a complete high/low voltage control system and a customizable thin-profile landscape-type outdoor enclosure with multimedia capabilities.
This product is composed of two main parts:
Underground section: A high-protection-level underground transformer and underground transformer chamber.
Above-ground section: High/low voltage switchgear and an anti-corrosion landscape enclosure.
It is widely used in modern urban environments where visual integration, compactness, and performance are required. The transformer capacity ranges from 30 kVA to 1600 kVA, making the product highly versatile and fully standardized.
Altitude: ≤1000m for high voltage; ≤2000m for low voltage
Ambient temperature:
Max temperature: +40°C
Min temperature: -45°C
Max monthly average: +30°C
Max yearly average: +20°C
Installation site:
Free from explosive, corrosive liquids, gases, or dust
No violent vibration or impact
Allows partial or full submersion in water for certain periods
Seismic tolerance (ground acceleration):
Horizontal ≤ 3 m/s²
Vertical ≤ 1.5 m/s²
Power waveform: Approximate sine wave
Power symmetry: For three-phase units, voltages should be approximately symmetrical
★ Special customized versions available for extreme environmental conditions
GB 311.1-1997: Insulation coordination for high-voltage transmission equipment
GB/T 2900.1, 2900.20: Electrotechnical terminology
GB 3906-1991: 3–35kV AC metal-enclosed switchgear
GB 4208-1993: Ingress protection rating (IP code)
GB/T 7251.1-2005: Low-voltage switchgear and controlgear assemblies
GB/T 10233-2005: Basic testing methods for LV equipment
GB/T 11022-1999: Common technical requirements for high-voltage switchgear
GB/T 17467-2010: HV/LV prefabricated substations
GB/T 16927.1-1997: General requirements for high-voltage test techniques
GB/T 16935.1-1997: Insulation coordination for low-voltage systems
JB/T 10544-2006: Underground transformers
Operating Conditions